4G Smart Moulded-Case Circuit Breaker (MCCB) product image
IOTB2LM LTE(4G)

4G Smart Moulded-Case Circuit Breaker (MCCB)

Product name
4G Smart Moulded-Case Circuit Breaker (MCCB)
Product model
IOTB2LM LTE(4G)
Communication
4G
Rated voltage
AC380/400/415V (three-phase)
Current range
50-125A / 100-250A / 160-400A / 250-630A / 320-800A
Application point
Main-distribution circuit / Critical load
Section

Core functions

Main-distribution protection

Protection status and abnormal events for main-distribution circuits and critical loads can be viewed in one place.

Selectable current range

Covers the common moulded-case circuit breaker distribution range from 50 A to 800 A, making it easy to select based on cabinet capacity.

Remote monitoring

Connects via 4G, Wi-Fi, or RS485 so the status of key nodes can be included in the operations workflow.

Automatic reclosing

For project-based distribution applications that need fault-recovery assessment and coordinated remote response.

Section

Product details

4G Smart Moulded-Case Circuit Breaker (MCCB)

Applications

The smart moulded-case circuit breaker (MCCB) protects main-distribution circuits and critical loads. The IOTB2LM LTE(4G) connects over 4G, with frame sizes covering 125 A, 250 A, 400 A, 630 A and 800 A.

Selection overview

Item
Product series
Specification
IOTB2LM LTE(4G) smart moulded-case circuit breaker series
Item
Communication
Specification
LTE(4G)
Item
Applicable system
Specification
Three-phase four-wire supply / consumer systems with a directly earthed neutral
Item
Rated operational voltage
Specification
Ue AC380/400/415V 50Hz
Item
Poles
Specification
3P+N / 4P
Item
Model designation
Specification
125 / 250 / 400 / 630 / 800 = frame current ratings; S / M / H = normal / standard / high breaking capacity; 3N = 3P+N (N pole non-switching); 4 = 4P (N pole switching)
Item
Breaking-capacity class
Specification
S / M / H
Item
Applicable standards
Specification
GB/T14048.2; GB/T14048.4; GB/T32902
ItemSpecification
Product seriesIOTB2LM LTE(4G) smart moulded-case circuit breaker series
CommunicationLTE(4G)
Applicable systemThree-phase four-wire supply / consumer systems with a directly earthed neutral
Rated operational voltageUe AC380/400/415V 50Hz
Poles3P+N / 4P
Model designation125 / 250 / 400 / 630 / 800 = frame current ratings; S / M / H = normal / standard / high breaking capacity; 3N = 3P+N (N pole non-switching); 4 = 4P (N pole switching)
Breaking-capacity classS / M / H
Applicable standardsGB/T14048.2; GB/T14048.4; GB/T32902

Frame size

Category
125 frame
Model/Specification
IOTB2LM LTE(4G)-125
Current / modules
50-125A
Category
250 frame
Model/Specification
IOTB2LM LTE(4G)-250
Current / modules
100-250A
Category
400 frame
Model/Specification
IOTB2LM LTE(4G)-400
Current / modules
160-400A
Category
630 frame
Model/Specification
IOTB2LM LTE(4G)-630
Current / modules
250-630A
Category
800 frame
Model/Specification
IOTB2LM LTE(4G)-800
Current / modules
320-800A
CategoryModel/SpecificationCurrent / modules
125 frameIOTB2LM LTE(4G)-12550-125A
250 frameIOTB2LM LTE(4G)-250100-250A
400 frameIOTB2LM LTE(4G)-400160-400A
630 frameIOTB2LM LTE(4G)-630250-630A
800 frameIOTB2LM LTE(4G)-800320-800A

Main technical parameters

Item
Rated insulation voltage Ui
Specification
AC1000V
Item
Rated impulse withstand voltage Uimp
Specification
12000V / 12kV
Item
Overload long-time delay setting
Specification
(0.4-1)In
Item
Short-circuit short-time delay protection
Specification
Ir2: 2Ir1-10Ir1; ts: 0.1-1.0 s / OFF; factory setting: 6Ir1 / 0.4 s
Item
Short-circuit instantaneous protection
Specification
Ir3: 4Ir1-12Ir1; factory setting: 10Ir1
Item
Residual operating current
Specification
30mA (non-time-delay only) / 50 / 75 / 100 / 200 / 300 / 500 / 800 / 1000mA adjustable
Item
Maximum non-tripping time
Specification
0.06 / 0.1 / 0.2s selectable
Item
Rated ultimate short-circuit breaking capacity Icu
Specification
125/250 frames: S50 / M65 / H100; 400/630/800 frames: S50 / M70 / H100
Item
Rated service short-circuit breaking capacity Ics
Specification
S35/M50/H70
Item
Short-time withstand current Icw
Specification
10kA / 1s
Item
Utilization category
Specification
Category B
Item
Residual short-circuit making and breaking capacity I△m
Specification
25% Icu
Item
Reclosing interval
Specification
20-60s
Item
Installation conditions
Specification
Altitude ≤2000m; maximum mounting inclination ±5°; installation category III for the main circuit, II for auxiliary / control circuits
Item
Operating environment
Specification
-10 °C to +45 °C; temperature variation within 24h not exceeding 35K; relative air humidity not exceeding 50% at +40 °C; no media presenting an explosion hazard; pollution degree 3
ItemSpecification
Rated insulation voltage UiAC1000V
Rated impulse withstand voltage Uimp12000V / 12kV
Overload long-time delay setting(0.4-1)In
Short-circuit short-time delay protectionIr2: 2Ir1-10Ir1; ts: 0.1-1.0 s / OFF; factory setting: 6Ir1 / 0.4 s
Short-circuit instantaneous protectionIr3: 4Ir1-12Ir1; factory setting: 10Ir1
Residual operating current30mA (non-time-delay only) / 50 / 75 / 100 / 200 / 300 / 500 / 800 / 1000mA adjustable
Maximum non-tripping time0.06 / 0.1 / 0.2s selectable
Rated ultimate short-circuit breaking capacity Icu125/250 frames: S50 / M65 / H100; 400/630/800 frames: S50 / M70 / H100
Rated service short-circuit breaking capacity IcsS35/M50/H70
Short-time withstand current Icw10kA / 1s
Utilization categoryCategory B
Residual short-circuit making and breaking capacity I△m25% Icu
Reclosing interval20-60s
Installation conditionsAltitude ≤2000m; maximum mounting inclination ±5°; installation category III for the main circuit, II for auxiliary / control circuits
Operating environment-10 °C to +45 °C; temperature variation within 24h not exceeding 35K; relative air humidity not exceeding 50% at +40 °C; no media presenting an explosion hazard; pollution degree 3

Monitoring, recording and maintenance

Item
Operation monitoring
Specification
Displays operating status, rated current, residual current setting, phase voltage / phase current, leakage current, active / reactive power, energy, power factor, frequency, temperature (optional) and harmonics
Item
Metering accuracy
Specification
Current and voltage accuracy is class 0.5S; active and reactive power are class 1.
Item
Records and traceability
Specification
Supports querying the tripped phase, trip cause, trip time and historical records, with trip-count statistics.
Item
Parameter maintenance
Specification
Protocol, address, baud rate, date and time, contrast, total energy reset and protection parameters can be set
Item
External interface
Specification
Supports active / reactive energy pulse output, RS485, external opening / closing control, an auxiliary interface and an external 485 power supply terminal
ItemSpecification
Operation monitoringDisplays operating status, rated current, residual current setting, phase voltage / phase current, leakage current, active / reactive power, energy, power factor, frequency, temperature (optional) and harmonics
Metering accuracyCurrent and voltage accuracy is class 0.5S; active and reactive power are class 1.
Records and traceabilitySupports querying the tripped phase, trip cause, trip time and historical records, with trip-count statistics.
Parameter maintenanceProtocol, address, baud rate, date and time, contrast, total energy reset and protection parameters can be set
External interfaceSupports active / reactive energy pulse output, RS485, external opening / closing control, an auxiliary interface and an external 485 power supply terminal

Display, settings and connection

Item
Display and settings
Specification
The local display shows rated current, residual current setting, operating status and time, voltage / current, leakage current, power, energy, power factor, frequency and temperature (optional)
Item
Electronic protection
Specification
Overload long-time delay, short-circuit short-time delay / instantaneous, residual current, reclosing, over- and under-voltage, phase loss, neutral loss and overtemperature (optional) can all be configured
Item
Panel buttons
Specification
Open, close, menu, confirm, back, up/down, test and alarm buttons are used for local operation
Item
Local operation
Specification
The handle, buttons and display area are used for on-site opening and closing, reset, parameter viewing and commissioning
Item
Installation and wiring
Specification
The circuit breaker should be mounted vertically; the upper terminals are the main-circuit incoming side, the lower terminals are the outgoing side, and the neutral must be connected to the N terminal
Item
Communication interface
Specification
The 4G / WiFi / RS485 versions can connect to the platform or an on-site system according to network conditions
Item
Certification and delivery
Specification
The 125 / 250 and 400 / 630 / 800 frame sizes each carry the corresponding 3C / CQC certificates.
ItemSpecification
Display and settingsThe local display shows rated current, residual current setting, operating status and time, voltage / current, leakage current, power, energy, power factor, frequency and temperature (optional)
Electronic protectionOverload long-time delay, short-circuit short-time delay / instantaneous, residual current, reclosing, over- and under-voltage, phase loss, neutral loss and overtemperature (optional) can all be configured
Panel buttonsOpen, close, menu, confirm, back, up/down, test and alarm buttons are used for local operation
Local operationThe handle, buttons and display area are used for on-site opening and closing, reset, parameter viewing and commissioning
Installation and wiringThe circuit breaker should be mounted vertically; the upper terminals are the main-circuit incoming side, the lower terminals are the outgoing side, and the neutral must be connected to the N terminal
Communication interfaceThe 4G / WiFi / RS485 versions can connect to the platform or an on-site system according to network conditions
Certification and deliveryThe 125 / 250 and 400 / 630 / 800 frame sizes each carry the corresponding 3C / CQC certificates.